In the preventive testing of power systems, measuring the conductive circuit resistance of high-voltage switches, GIS (Gas Insulated Switchgear), and busbars is a crucial step. During long-term operation, contact oxidation, insufficient contact pressure, or mechanical wear can increase contact resistance. If contact resistance exceeds the standard, a large amount of heat will be generated when high current flows through, potentially leading to equipment burnout.
Traditional measurement methods often use DC double-arm bridges or micro-current measurements, but due to the small test current, they cannot effectively break down the oxide film on the contact surface, resulting in inaccurately high readings. The KDHL-100A Circuit Resistance Tester adopts high-current constant current output and digital filtering technology to effectively solve this on-site pain point.
I. Working Principle: Kelvin Four-Wire Method and High-Current Constant Current Output
The core measurement principle of the KDHL-100A is based on the Kelvin four-wire method (four-terminal measurement). The instrument has a built-in high-power switching power supply that outputs a constant DC high current of 100A. The current flows into the tested circuit through dedicated current cables, while the voltage drop across the circuit is collected through another pair of voltage cables.
According to Ohm's law (R=U/IR=U/I), since the high-precision AD converter inside the tester only collects voltage signals and almost no current flows through the voltage cables, the resistance of the test cables themselves is not superimposed on the measurement result, completely eliminating the influence of lead resistance and contact resistance. The high current of 100A can instantly break down the oxide film on the contact surface, truly reflecting the tiny resistance value of the conductive circuit.
II. Core Technical Features
Multi-range Current Output and Wide Measuring Range: The equipment supports multiple test current outputs such as 100A and 200A (optional), with a measurement range covering 0~1999.9μΩ, fully meeting the testing requirements of various high-voltage switches, circuit breakers, and busbars.
High Precision and Digital Filtering: It combines advanced hardware and digital filtering technologies to effectively suppress strong on-site electromagnetic interference. In the complex electromagnetic environment of substations, it still ensures stable readings with minimal data fluctuation.
Intelligent Protection Mechanism: Equipped with overcurrent, overheat, and open-circuit protection functions. When the test time is too long or the circuit is not properly connected, the instrument will automatically cut off the output and alarm, preventing high current from burning the test cables or damaging the instrument.
Integrated Portable Design: Housed in an engineering plastic case, it is compact. The panel is equipped with a high-brightness LCD screen, clearly visible even in strong light. It has a built-in high-capacity lithium battery (or AC220V power supply), supporting long-term continuous testing in outdoor conditions without a power supply.
III. On-site Application and Operation Key Points
In actual on-site testing, the correct wiring method is the prerequisite for ensuring accurate data:
Clean the Contact Surface: Before testing, the oxide layer on the switch terminals or busbar contact surfaces must be polished with sandpaper or a wire brush to ensure good contact between the test clamps and the equipment.
Sequence of Voltage and Current Cables: Strictly follow the four-wire method. Clamp the voltage test cables inside the current test cable jaws (the side closer to the equipment under test). It is strictly forbidden to cross or reverse the voltage and current cables.
Test Time Control: Due to the high current of 100A, long-term power-on will cause the test cables to heat up and soften. The single measurement time is recommended to be controlled within a few seconds to a dozen seconds. The output can be disconnected once the reading is stable.
Conclusion
The KDHL-100A Circuit Resistance Tester provides accurate data support for the contact status of high-voltage switchgear through its high-current constant current source and four-wire measurement technology. Standardized wiring and reasonable operation are the keys to maximizing the instrument's performance.
For specific technical parameters or selection schemes of the KDHL-100A, please contact us.
Wuhan Kedian Zhongwei Electric Co., Ltd.
Tel: 027-86861986
Email: whkdz@163.com